地磁感应电流监测装置在西北750 kV电网的应用
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
磁暴在输电线路引发的地磁感应电流(GIC)频率为0.001~0.100 Hz,这种准直流的GIC将造成变压器直流偏磁饱和,引发电网保护误动作和停电事故。为了分析、研究GIC对西北750 kV电网的影响,开发研制了电网GIC监测装置。装置在官亭、兰州东750 kV变电站的应用表明,研制的装置能有效地测量电网准直流、随机性信号,并且具有数据处理量少、节约存储空间等优点。
Geo-magnetically induced currents(GIC) are triggered by geomagnetic storms,the frequency of which ranges from 0.001 Hz to 0.100 Hz.GIC will cause DC bias saturation of transformers,unnecessary relay tripping and blackouts.To analyze and study effects of GIC on Northwest 750 kV power grid,GIC monitoring device is developed for power grids.The application of devices in Guanting and Eastern Lanzhou 750 kV substations indicated that the devices can effectively measure random quasi-dc signals in power grids,and have advantages such as less data processing volume and memory space.
引文
[1]刘连光,刘春明,张冰,等.我国广东电网的几次强磁暴影响事件[J].地球物理学报,2008,51(4):976-981.
    [2]刘连光.磁暴对中国电网的影响[J].电网与水力发电进展,2008,24(5):1-6.
    [3]Albertson V D,Thorson J M,Claylon R E,et al.Solar Induced Currents in Power System:Cause and Effects[J].IEEE Transcation on Power Apparatus and Systems,1973,PAS-92(2):471-477.
    [4]Albertson V D,Thorson J M,Mikes S A,et al.The Effects of Geomagnetic Storms on Electric Power System[J].IEEE Transaction on Power Apparatus and System,1974,PAS-93(4):1031-1044.
    [5]蒯狄正,刘成民,万达.直流偏磁对变压器影响的研究[J].江苏电机工程,2004,23(3):1-5.
    [6]Kappenman J G,Albertson V D.Bracing for the Geomag-netic Storms[J].IEEE Spectrum,1990,27(3):27-33.
    [7]Risto Pirjola.Geomagnetically Induced Currents During Mag-netic Storms[J].IEEE Transaction on Plasma Science,2000,28(6):1867-1873.
    [8]中国地震局监测预报司.地震电磁数字观测技术[M].北京:地震出版社,2002.
    [9]贾秀芳,李宝树,黄辉福.霍尔磁势平衡原理在检测直流小电流中的应用[J].华北电力大学学报,1999,26(4):15-18.

版权所有:© 2023 中国地质图书馆 中国地质调查局地学文献中心