文摘
Heat transfer and pumping power of GNPs nanofluid is strongly dependent on heat input. The lowest base temperature is found to be 36.82 °C using GNPs nanofluids. The lowest convective thermal resistance is observed 0.049 K/W using GNPs nanofluids. The maximum pumping power is observed 0.041 W at heat flux of 47.96 KW/m2. 21.51%, 15.38% and 13.76% CHT enhancement is found at heat flux of 47.96 KW/m2, 59.95 KW/m2, and 71.94 KW/m2.