Field tests of centralized and decentralized ventilation units in residential buildings - Specific fan power, heat recovery efficiency, shortcuts and volume flow unbalances
详细信息    查看全文
文摘

Field tests with 20 centralized and 60 decentralized mechanical ventilation systems.

High deviations between supply and exhaust of up to 60%.

The mean total recirculation was 6.5% for centralized and 13% for decentralized devices.

The specific fan power was measured with 0.475 Wh/m3 for centralized and 0.22 Wh/m3 for decentralized systems.

The mean temperature change rate was 0.65 for centralized systems and 0.7 for decentralized systems.