基于频域介电谱分析的高压套管受潮状况评估方法
详细信息    查看全文 | 推荐本文 |
  • 英文篇名:Evaluation Method of Moisture State for High Voltage Bushing Based on Frequency Domain Dielectric Spectrum Analysis
  • 作者:李文震 ; 师宽 ; 冯新文 ; 王东升 ; 曹永东 ; 张杰 ; 李飞
  • 英文作者:LI Wenzhen;CHEN Shikuan;FENG Xinwen;WANG Dongsheng;CAO Yongdong;ZHANG Jie;LI Fei;State Grid East Inner Mongolia Electric Power Company Limited;Wuhan NARI Limited Liability Company of State Grid Electrical Power Research Institute;
  • 关键词:高压套管 ; 油纸绝缘 ; 频域介电谱 ; 受潮状况
  • 英文关键词:high voltage bushing;;oil-paper insulation;;frequency domain spectroscopy;;moisture state
  • 中文刊名:JYCT
  • 英文刊名:Insulating Materials
  • 机构:国网内蒙古东部电力有限公司;国网电力科学研究院武汉南瑞有限责任公司;
  • 出版日期:2019-02-21 17:04
  • 出版单位:绝缘材料
  • 年:2019
  • 期:v.52
  • 语种:中文;
  • 页:JYCT201902013
  • 页数:4
  • CN:02
  • ISSN:45-1287/TM
  • 分类号:76-79
摘要
为了完善现场条件下高压套管的受潮状况评估方法,针对高压套管的频域介电谱(FDS)展开研究。通过测量4支高压套管的FDS曲线,评估了套管绝缘的含水量;将套管的FDS曲线折算成介损温度曲线,与典型的介损温度特征曲线进行比对,并结合FDS诊断图谱分析套管的FDS测量结果。结果表明:FDS曲线可以灵敏地反映套管的受潮状况,根据高频段的tanδ最小值可以定性分析套管的受潮状况,利用MODS软件中的数据库对FDS曲线进行拟合可以定量评估套管的受潮状况,且FDS测试结果与介损温度测试结果具有一致性。证明频域介电谱分析法可用于现场评估诊断高压套管的受潮状况。
        In order to improve the on-site evaluation method of moisture state for high voltage bushing,the frequency domain dielectric spectroscopy(FDS) of high voltage bushing was studied. The FDS curves of four high voltage bushings were tested to evaluate the water content of bushing insulation. The FDS curves of bushing was converted to dielectric loss temperature characteristics curve and compared with the typical dielectric loss temperature characteristics curve, and then analyzed combing FDS diagnosis spectrum. The results show that the FDS curves can reflect the moisture state of bushing sensitively.According to the minimum of tanδ at high frequency, the moisture state of bushing can be analyzed qualitatively. Using the database in MODS software to fit the FDS curves can evaluate the moisture state of bushing, and the FDS test results are consistent with the results of dielectric loss temperature test. It is proved that FDS analysis method can be used for the on-site diagnosis of moisture state of high voltage bushing.
引文
[1]冯达,柯春俊,吴锴.基于频域介电谱分析的油纸套管状态评估仿真[J].变压器,2015,52(4):52-54.
    [2]杨雁,杨丽君,徐积全,等.用于评估油纸绝缘热老化状态的极化/去极化电流特征参量[J].高电压技术,2013,39(2):336-341.
    [3]李明华,董明,严璋.一种新的绝缘测试方法--回复电压法[J].高电压技术,2002,28(8):43-45.
    [4]GUBANSKI S M,BOSS P,CSEPES G,et al.Dielectric response methods for diagnostics of power transformers[C]//IEEE Electrical Insulation Magazine,2003,19(3):12-18.
    [5]李洁,侯英洒,赵建利,等.温度和老化程度对油纸绝缘频域谱的影响研究[J].高压电器,2016,52(11):157-162.
    [6]陈名铭,韦国,刘君,等.温度和水分对变压器油纸绝缘系统频域介电谱特性的影响[J].绝缘材料,2012,45(1):51-67.
    [7]杜振波,聂德鑫,张连星,等.基于频域介电谱分析的高压套管绝缘状态评估[J].高压电器,2013,49(11):6-11.
    [8]袁泉,胡舰,周天春,等.温度对变压器用油纸绝缘老化的频域介质响应的试验研究[J].高压电器,2013,49(2):74-79.