大型直流电压发生器塔架结构地震响应分析
详细信息 本馆镜像全文    |  推荐本文 | | 获取馆网全文
摘要
本文以某一大型直流电压发生器塔架结构为例,建立有限元计算模型,采用调幅正弦五波、Taft地震波、El-Centro地震波、云南澜沧地震波和正弦三波5种地震动输入,通过数值计算,讨论了不同输入地震波对于结构抗震设计的影响。结果表明,地震作用效应在这类特种结构的组合响应中起重要影响,采用调幅正弦五波、正弦三波作为地震输入,过分夸大了实际的地震作用效应。最后,对这类特种结构的输入地震动提出了相应建议。
A finite element model for the structure of a large DC voltage generator tower is established in this paper.Five seismic waves,i.e.five-amplitude-modulation-sine wave,Taft earthquake wave,El-Centro seismic wave,Yunnan Lancang seismic waves and three-sine wave,are taken as the seismic input for the seismic response analysis of the structure.The influence of different input wave on the seismic design of the structure is discussed through numerical analysis.The numerical results show that the seismic action effect has important influence on the final combination responses of this particular structure and the seismic action effect is overestimated when using five-amplitude-modulation-sine wave and three-sine wave as seismic input.Finally,some suggestions of seismic input for this type of particular structure are proposed.
引文
贺晓晖,楼梦麟,2008.大型特高压直流发生器结构地震时程反应分析.结构工程师,24(6):100-106.
    楼梦麟,陈群丽,1999.考虑提离滑移的电压发生器塔架结构地震反应分析.地震工程与工程振动,19(1): 164-171.
    谢礼立,翟长海,2003.最不利设计地震动研究.地震学报,6(3):11-15.
    赵成刚,冯启民,1994.生命线地震工程.北京:地震出版社.
    中华人民共和国国家标准,2001建筑结构荷载规范(GB 50009-2001).北京:中国建筑工业出版社.
    中华人民共和国国家标准,1996.电力设施抗震设计规范(GB 50260-96).北京:中国计划出版社.
    R.W.克拉夫,J.彭金著,王光远译,1981.结构动力学.北京:科学出版社.

版权所有:© 2023 中国地质图书馆 中国地质调查局地学文献中心