用户名: 密码: 验证码:
Cumulative exergy analysis of ice thermal storage air conditioning system
详细信息查看全文 | 推荐本文 |
摘要
Based on the cumulative exergy analysis method, the effect of incorporating the Ice Thermal Storage (ITS) air conditioning system in power supply is analyzed. Not only the cumulative exergy of air conditioning system is considered, but also that of the processes consuming the power generated by the same peak regulating unit. The results show that the total cumulative exergy consumption of all processes consuming the power supplied by the peak generating unit, increases as the ITS system is applied. However, the average cumulative exergy variation, which is the ratio between the increment of the cumulative exergy consumption (螖CEx) and the cooling load of the ITS system (QITS), decreases slightly as QITS increases. It exhibits a linear relationship with the operating load of the power generating unit and QITS. And, it decreases as either of the two parameters increases. These results are verified by two case studies.

© 2004-2018 中国地质图书馆版权所有 京ICP备05064691号 京公网安备11010802017129号

地址:北京市海淀区学院路29号 邮编:100083

电话:办公室:(+86 10)66554848;文献借阅、咨询服务、科技查新:66554700