Experimental Study on Corrosion Control Using Coking Wastewater as Circulating Cooling Water
详细信息   
摘要
///The coking wastewater drainage will bring severe water environmental pollution, so it is necessary to change the coking wastewater into resource. The reuse of pre-treated coking wastewater as make-up water for circulating cooling system is an important way. To prevent the circulating cooling system corrosion, the characteristic and the corrosion control technology and the effect of the classic corrosion inhibitors in the circulating cooling water system were studied by static experiment and dynamic experiment based on water quality stabilization theory. The results indicate that the corrosion in circulating cooling system is mainly spot corrosion caused by pollutants in coking wastewater, and the corrosion inhibition technology on the model of precipitated membrane based on phosphor series should be preferred.