摘要
针对某型号252 kV气体绝缘金属封闭开关设备(gas insulated metal-enclosured switchgear,GIS)灭弧室故障和设备解体过程发现的问题,判断触头接触不良,仅弧触头形成接触、主触头未形成接触是造成故障的直接原因。利用ANSYS软件建立了故障灭弧室1∶1三维有限元模型,考虑了接触电阻随温度变化的特性,进行电热耦合场及静电场仿真,获得灭弧室内的三维温度场及电场分布,如内部载流系统的温升、断口间和屏蔽罩的电场分布等,从而揭示故障中放电路径的形成原因,还原故障过程,为该型号GIS灭弧室的安全运行提供了理论支撑。
Problems found in the fault of one typed 252 kV GIS arc extinguishing chamber and its disassembly process are analyzed. The bad contact of contacts been discovered is the direct reason for causing the fault. A 1∶1 3 D finite element model of the faulted arc extinguishing chamber is built in ANSYS. The temperature dependence of the contact resistance is considered. Simulations on electric-thermal coupling field and electrostatic field are made. The 3 D temperature field and electric field distribution in the arc extinguishing chamber are obtained, such as temperature rise of the current carrying system, electric field distribution of contacts and shielding cases. Thus, the forming of discharge paths is revealed and the fault process is restored, which can provide theoretical supporting for safe operation of this typed GIS arc extinguishing chamber.
引文
[1] 王流火,林博楚,吕鸿.一起220 kV GIS断路器放电故障分析与试验研究 [J].广东电力,2015,27(2):97-100.WANG Liuhuo,LIN Bochu,Lü Hong.Analysis and experimental research on discharge fault of 220 kV GIS breaker [J].Guangdong Electric Power,2015,27 (2):97-100.
[2] 张乔根,文韬,赵军平,等.大容量GIS现场冲击试验问题探讨 [J].广东电力,2018,30 (8):37-43.ZHANG Qiaogen,WEN Tao,ZHAO Junping,et al.Discussion on problems of on-site impulse test of GIS with large capacitance [J].Guangdong Electric Power,2018,30(8):37-43.
[3] 李庆民,王健,李伯涛,等.GIS/GIL中金属微粒污染问题研究进展 [J].高电压技术,2016,42(3):849-860.LI Qingmin,WANG Jian,LI Botao,et al.Review on metal particle contamination in GIS/GIL [J].High Voltage Engineering,2016,42(3):849-860.
[4] 黎斌.SF6高压电器设计[M].4版.北京:机械工业出版社,2015.
[5] 厉天威,罗兵,傅明利,等.550 kV交流滤波器断路器灭弧室电场计算 [J].南方电网技术,2016,10(1):26-31.LI Tianwei,LUO Bing,FU Mingli,et al.Electric field calculation on arc-extinguishing chamber of 550 kV AC filter circuit breaker [J].Southern Power System Technology,2016,10(1):26-31.
[6] 王程嘉,唐力,李歆蔚,等.金属微粒对交流滤波器断路器灭弧室电场的影响 [J].高压电器,2017,53(6):105-112.WANG Chengjia,TANG Li,LI Xinwei,et al.Effect of metallic particles on electric field of AC filter circuit breaker arc-extinguishing chamber [J].High Voltage Apparatus,2017,53(6):105-112.
[7] 和彦淼,张俊民,袁海文.高压SF6断路器灭弧室电场优化与分析 [J].高压电器,2006,42(6):442-444,449.HE Yanmiao,ZHANG Junmin,YUAN Haiwen.Electric field optimization and analysis on high voltage SF6 circuit breaker [J].High Voltage Apparatus,2006,42(6):442-444,449.
[8] 刘超,阮江军,黄道春,等.考虑接触电阻下的电缆接头热点温度[J].高电压技术,2016,42(11):3634-3640.LIU Chao,RUAN Jiangjun,HUANG Daochun,et al.Hot spot temperature of cable joint considering contact resistance [J].High Voltage Engineering,2016,42(11):3634-3640.
[9] 纽春萍,强若辰,荣命哲,等.弹簧触指的稳态温升仿真与实验研究[J].高压电器,2015,51(3):8-14.NIU Chunping,QIANG Ruochen,RONG Mingzhe,et al.Simulation and experimental research on temperature rise of spring contact in steady state[J].High Voltage Apparatus,2015,51(3):8-14.
[10] 孙国霞,舒乃秋,吴晓文,等.基于多物理场耦合的气体绝缘母线触头接触温升有限元计算[J].电工技术学报,2013,28(增刊2):408-413.SUN Guoxia,SHU Naiqiu,WU Xiaowen,et al.Finite element analysis of contact temperature rise in gas insulated busbars based on coupled multi-physics[J].Transactions of China Electrotechnical Society,2013,28(S2):.408-413.
[11] 金虎,彭在兴,王颂,等.252 kV三相共箱GIS母线壳体温度场分布特性研究[J].高压电器,2017,53(12):20-25.JIN Hu,PENG Zaixing,WANG Song,et al.Research on temperature field distribution characteristics of 252 kV three-phase enclosed gis bus bar shell [J].High Voltage Apparatus,2017,53(12):20-25.
[12] 许良军,芦娜,林雪燕,等.电接触理论、应用与技术[M].北京:机械工业出版社,2010.
[13] DL/T 539—2016,高压开关设备和控制设备标准的共用技术要求[S].
[14] 程建伟,赵林杰,孙夏青,等.实际运行电压下特高压换流变压器阀侧套管电场分布研究[J].南方电网技术,2017,11(5):1-8.CHENG Jianwei,ZHAO Linjie,SUN Xiaqing,et al.Simulation analysis and countermeasures of typical insulation faults for ±800 kV DC[J].Southern Power System Technology,2017,11(5):1-8.
[15] 姚斌,施世鸿,陈荔.±1 100 kV特高压直流换流站直流场导体的电磁计算与设计选型 [J].南方能源建设,2016,3(4):37-41.YAO Bin,SHIShihong,CHEN Li.Electromagnetic environment calculation and design of ±1 100 kV DC conductor in UHVDC converter station [J].Southern Energy Construction,2016,3(4):37-41.
[16] 刘志刚,林莘,耿英三.SF6罐式高压断路器三维电场计算与分析 [J].高电压技术,2003,29(3):27-28,30.LIU Zhigang,LIN Xin,GENG Yingsan.The calculation and analysis of three-dimension electric field of SF6 tank-type circuit breaker [J].High Voltage Engineering,2003,29(3):27-28,30.