70% of annual electric consumption lies in low PLR range of 0% through 50%.
Sequential chiller staging control algorithm showed the lowest annual electric consumption.
In conclusion, sequential control should be applied during the intermediate season.
Uniform control chiller staging algorithm should be applied during the cooling season.