Conversion of a direct to an indirect commercial (HFC134a/CO2) cascade refrigeration system: Energy impact analysis
详细信息    查看全文
  • 关键词:Cascade ; F-Gas ; CO2 ; HFC134a ; Energy analysis
  • 刊名:International Journal of Refrigeration
  • 出版年:2017
  • 出版时间:January 2017
  • 年:2017
  • 卷:73
  • 期:Complete
  • 页码:183-199
  • 全文大小:5056 K
  • 卷排序:73
文摘
Conversion of a direct to an indirect HFC134a/CO2 cascade system is analysed experimentally. Refrigeration system supplies cooling needs of two cabinets (2 and −20 °C) inside a climatic chamber. A decrease between 1.9 to 3.5 K of the evaporating temperature of the high temperature cycle has been measured. When using propylene-glycol/water mixture (40% vol.) as secondary fluid energy consumption increases from 7.6 to 14.0% regards the direct system. When using Temper −20 as secondary fluid energy consumption varies from −0.3 to 11.1% regards the direct system.