This paper studies how to deal with natural convective heat transfer for a radiator in order to simplify the simulations.
By adding user-defined wall functions the number of cells can be reduced considerably compared with the k-ω SST turbulence model.
Compared to manufacturer data the error of the model is less than 0.2% for the investigated radiator height and temperature.