A comparison of trans-admittance and characteristic impedance as metrics for detection of winding displacements in power transformers
详细信息    查看全文
文摘
Transfer function signatures are commonly used in condition monitoring analysis to give early indications of winding movement in power transformers. This paper presents a comparison of the use of trans-admittance (frequency response analysis, FRA), presently the industry standard, and characteristic impedance (transmission line diagnostics, TLD), a new method, as signatures for the detection of winding displacements in power transformers. To facilitate the comparison, a computer based winding model based on a multi-phase transmission line system was developed and different winding deformations were analyzed. The results show that TLD has a higher degree of sensitivity and can be used to augment the ability to classify different types of distortions currently diagnosed by FRA.