A novel MMC control scheme to increase the DC voltage in HVDC transmission systems
详细信息    查看全文
文摘
Higher DC voltage operation of MMC incorporating third harmonic injection is proposed. DC voltage is increased by 13.4% while SM number per arm and SM capacitor voltage remain unchanged. DC current is lowered and DC transmission loss is expected to reduce by 22.2%. Station conduction losses, semiconductor current stresses, and phase energy variation are also reduced.

© 2004-2018 中国地质图书馆版权所有 京ICP备05064691号 京公网安备11010802017129号

地址:北京市海淀区学院路29号 邮编:100083

电话:办公室:(+86 10)66554848;文献借阅、咨询服务、科技查新:66554700