Effect of switching off unidirectional downflow systems of operating theaters during prolonged inactivity on the period before the operating theater can safely be used
详细信息    查看全文
文摘
After starting up the system, the protected area achieved the required degrees of protection within 20 minutes (95% upper confidence limit). After starting up the system, a stable temperature difference was achieved within 23 minutes (95% upper confidence limit). Both findings lie well within the period of 25 minutes normally required for preparations before the start of surgical procedures. Switching off the ventilation system during prolonged inactivity (during the night and weekend) has no negative effect on the air quality in unidirectional downflow operating theaters during normal operational hours and can result in saving energy, up to 70% of the energy consumption compared with systems that function on full capacity continuously, and therefore costs.

© 2004-2018 中国地质图书馆版权所有 京ICP备05064691号 京公网安备11010802017129号

地址:北京市海淀区学院路29号 邮编:100083

电话:办公室:(+86 10)66554848;文献借阅、咨询服务、科技查新:66554700