Available transfer capability calculation considering voltage stability margin
详细信息查看全文 | 推荐本文 |
摘要
To make the electricity trades carry out successfully, the calculation of available transfer capability (ATC) must coordinate the relationship between the security and economic benefits. In this paper, a model for ATC calculations accorded with trade-off mechanism in electricity market was set up. The impact of branch outage contingency on the static voltage stability margin was analyzed, and contingency ranking was performed through sensitivity indices of branch flows with respect to the loading margin. Optimal power flow based on primal–dual interior point method was applied to obtain ATC when the N − 1 security constraints were included. The calculation results of IEEE 30-bus and IEEE 118-bus systems show that the proposed model and method are valid.