Assessment of Techniques for Measuring the Ventilation Rate, using an Experimental Building Section
详细信息查看全文 | 推荐本文 |
摘要
A full-scale, laboratory building section at Silsoe Research Institute was adapted to simulate cross-ventilating airflow patterns representative of those that develop in naturally ventilated, intensive livestock buildings. In the fully controlled, steady-state environment of the building section, the distribution of aerial pollutants and/or tracers was shown to depend on source location and ventilation rate. No single location within the building showed a consistently representative concentration of tracer that would be suitable for calculating ventilation rate by the constant release tracer method. Estimates of ventilation rate using the constant release tracer method, based on the average concentration of groups of six sampling locations within the building section, ranged from 93 to 119%of the ventilation rate measured using calibrated fan-wheel anemometers placed in the ventilation ducts. The best estimates of ventilation rate were obtained when the tracer concentration was measured at the perimeter (in the outlets and inlets) of the building section—these ranged from 99 to 109%of the ventilation rate measured using the fan-wheel anemometers.