Refrigerant circuitry design of fin-and-tube condenser based on entropy generation minimization
详细信息查看全文 | 推荐本文 |
摘要
This study presents a numerical model that is applicable to fin-and-tube condensers with complex refrigerant circuitry, and can be used to describe the exergy loss on the refrigerant side. The model was validated by comparing numerical results with experimental data for an R410A multi-pass condenser. The modeled and measured heat transfer rates were observed to agree with an error of less than 10%. Refrigerant-side performance was analyzed according to the design parameters using the numerical model, and appropriate performance evaluation criteria (PEC) were established for the refrigerant side of the condenser. A methodology was developed for refrigerant circuitry design based on entropy generation minimization (EGM). The resulting refrigerant circuit design enhanced heat transfer performance and lowered entropy generation in comparison to simple refrigerant circuitries.