The generator model consists of a four-degree-of-freedom rigid body, which is connected to an elastic shaft supported by isotropic bearings. The influence of magnetic pull is calculated for the case when the generator spider hub deviates from the centre of the generator rim. A nonlinear model of the magnetic pull is introduced to the model by radial forces and transverse moments.
In the numerical analysis input parameters typical for a 70 MW hydropower generator are used. Results are presented in stability and response diagrams. The results show that this type of rotor configuration can in some cases become unstable. Therefore, it is important to consider the distance between the centreline of generator spider hub and the centreline of generator rim.