Flash points of n-decanol
详细信息查看全文 | 推荐本文 |
摘要
In order to know accuracy of data in material safety data sheet (MSDS), the flash point of n-decanol was measured by using a Tag-closed tester, a Seta-flash-closed tester, a Pensky–Martens-closed tester and a Cleveland-open tester at the National Research Institute of Fire and Disaster (NRIFD) in Japan and the Korea Fire Equipment Inspection Corporation (KOFEIC) in Korea. The flash points measured were compared to data of the references. The flash points determined at NRIFD were similar to those of KOFEIC. However, the flash points 112 and 115 °C of n-decanol, measured at the NRIFD and 117 and 120 °C at the KOFEIC, respectively, were much different from those in MSDS and literatures. Therefore, manufacturers should be more careful when they make MSDS.

© 2004-2018 中国地质图书馆版权所有 京ICP备05064691号 京公网安备11010802017129号

地址:北京市海淀区学院路29号 邮编:100083

电话:办公室:(+86 10)66554848;文献借阅、咨询服务、科技查新:66554700