摘要
某电厂给水泵在非正常工况下发生了汽蚀故障,针对给水泵运行情况及故障现象,结合给水泵汽蚀发生原理分析认为,机组低压给水系统非正常运行工况是造成给水泵发生汽蚀的主要原因。提出了符合工程现场实际运行条件的低压给水系统及管路布置方式优化措施,供同类工程的设计以及电厂运行操作参考。
The feedwater pump cavitation fault occured under abnormal workingcondition in a power plant, according to the water pump running and fault phenomenon,combined with the pump cavitation occurring principle, thought that the abnormal operatingconditions of unit low pressure water supply system was the major cause of feed waterpump cavitation. Put forward a low-pressure water system conform to the actual operatingconditions and pipe layout optimization measures to provide a reference for similarengineering design and power plant operation.
引文
[1]程绍兵.王晓玲.防止汽机甩负荷过程中给水泵汽蚀的条件和措施[J].江西电力职工大学学报,2010,14(2):17-19.
[2]叶涛.热力发电厂[M].3版.北京:中国电力出版社,2011:92-93.
[3]郑李坤,薛东发,谢昌均.某1000 MW超超临界机组给水系统运行安全性分析[J].热力发电,2011,45(5):66-68.
[4]中华人民共和国住房和城乡建设部.GB 50049—2011小型火力发电厂设计规范[S].北京:中国计划出版社,2011:63-65.
[5]中华人民共和国住房和城乡建设部.GB 50764—2012电厂动力管道设计规范[S].北京:中国计划出版社,2012:84.
[6]赵志中.600 MW机组汽前泵性能优化与改进[J].内蒙古电力技术,2012,30(6):88-92.
[7]贾瑛,田树鹏,高健,等.汽动给水泵常见故障分析与处理[J].内蒙古电力技术,2011,29(2):59-60.
[8]魏然,王德意.水电机组汽蚀在线监测系统的研究[J].陕西电力,2001,29(2):49-50.
[9]刘立衡.350 MW超临界机组RB试验及控制策略分析[J].陕西电力,2013,41(8):75-78.
[10]张世荣,唐玉玲.给水泵汽蚀诊断模型的分析与控制[J].中南民族大学学报(自然科学版),2006,25(3):39-42.
[11]史海斌,马殿军.热力发电厂给水泵汽蚀现象、危害、原因及预防措施分析[J].知识经济,2010(23):103,113.