摘要
针对一起220kV开关拒动事故,阐明事故的原因和处理过程。计算和仿真结果分析表明,对于两组线圈共用铁芯的跳闸机构,开关误动概率会增大,在线圈接线顺序错误时开关还将无法动作,建议更换为可靠性更强的分体独立式结构的线圈。
To a 220 kV switch failure accident,the cause of the accident and the process of handling were introduced.Calculation and simulation showed that,for the tripping mechanism of the two sets of trip coils,the incorrect wiring of the coil will cause the switch to fail.At the same time,the tripping mechanism also raises the probability of the malfunction.It was recommended that the coil be replaced by a separate independent coil which has stronger reliability.
引文
[1]许守东,袁荣湘.玉溪变玉竹I回A相拒动原因分析及对策[J].电力系统保护与控制,2008,36(20):91-92.
[2]舒双焰,赵有铖,赵曼勇,等.“1.20”安顺电厂断路器拒动保护动作分析[J].电力系统保护与控制,2008,36(18):103-107.
[3]吴笃贵,赵斌,郭宝甫,等.PT二次误接线导致的定子接地保护拒动分析[J].电力系统保护与控制,2006,34(5):17-20.
[4]王国华.开关拒动对保护二次回路的危害及处理对策[J].电力系统保护与控制,2003,31(s1):61-62.
[5]高丕俭.220kV开关拒动事故分析及防范[J].工业安全与环保,2000(5):40-42.
[6]王驰.220kV开关拒动因素探讨及事故分析[J].科技信息,2013(15):391-391.
[7]向春梅.对一起主变开关拒动事故的思考[J].四川水力发电,2007,26(s2):131-132.
[8]张建新.广东电网2015年中开关拒动影响分析[J].科技信息,2010(25):774-775.
[9]张凯,杨佩佩,杨军亭,等.一起断路器机构故障引起的事故分析[J].电气技术,2016,17(10):142-145.
[10]糜作维.一起开关拒动事故的分析[J].电工电气,2009(10):63-64.
[11]彭凯,穆宏帅,刘平.一起电网事故的分析[J].电力系统保护与控制,2004(21):63-66.
[12]车兵,许家焰,徐晓春,等.智能变电站二次检修安措防误技术研究[J].电力系统保护与控制,2018,46(2):150-156.
[13]肖繁,王紫薇,张哲,等.基于状态监测的继电保护系统检修策略研究[J].电力系统保护与控制,2018,46(6):74-83.
[14]于晓军,刘志远,于小艳,等.基于双位置继电器构成的断路器非全相保护方法[J].电力系统保护与控制,2018,46(1):138-142.
[15]王锐彬,蔡莹.一起500kV断路器拒动事故的分析[J].黑龙江电力,2009,31(4):296-298.
[16]张静伟,庄泽宏.一起500kV开关误跳闸事故分析[J].电力系统保护与控制,2008,36(20):99-101.
[17]Qixin Chen,Xiangyu Zhao,Dahua Gan.Efficient maintenance testing in digital substations based on IEC 61850edition 2[J].Protection and Control of Modern Power Systems,2017(2):37.
[18]孟跃进.直流电磁铁磁路的分析和计算[J].上海电器技术,2008(4):22-25.
[19]王淑红,肖旭亮,熊光煜.直流恒力电磁铁特性[J].机械工程学报,2008,44(2):244-247.
[20]王强.螺管式电磁铁设计与仿真分析[D].长沙:湖南科技大学,2013.