循环水整体优化节电项目的成功应用
详细信息    查看全文 | 推荐本文 |
  • 英文篇名:Successful Application of Overall Optimization and Energy Saving Project for Circulating Water
  • 作者:马庆峰
  • 英文作者:MA Qingfeng;Water Supply and Drainage Plant of Qilu Petrochemical Co.,ltd;
  • 关键词:循环水系统 ; 节电 ; 循环水泵 ; 变频
  • 英文关键词:circulating water system;;electricity saving;;circulating water pump;;frequency conversion
  • 中文刊名:GWYT
  • 英文刊名:Energy Conservation in Petroleum & Petrochemical Industry
  • 机构:中国石化齐鲁石化股份有限公司供排水厂;
  • 出版日期:2019-03-22 11:32
  • 出版单位:石油石化节能
  • 年:2019
  • 期:v.9;No.97
  • 语种:中文;
  • 页:GWYT201903006
  • 页数:6
  • CN:03
  • ISSN:23-1572/TE
  • 分类号:7-8+25-28
摘要
齐鲁石化股份有限公司供排水厂针对乙烯水务车间第三循环水场(三循)存在的电耗高实际问题,于2015年开展了循环水整体优化节电改造项目,通过优化循环水系统节能运行模式、更新高效率节能型循环水泵、新增循环水泵和冷却风机变频设备及强化节能管理等一系列技改措施,用电量逐渐下降,节能效果逐步显现,达到了预期既定目标。三循自实施节能优化和自动控制系统改造并正式投入运行以来,工艺指标可控,设备参数正常,循环水泵和冷却风机运转平稳,系统高耗电现状得到明显改善,优化运行11个月共计节约电量545.7×10~4kWh,创效322.5万元,收到了较好的节电效果。
        with the increasing requirements of the state for energy conservation and consumption reduction in petrochemical enterprises,the water supply and drainage plant of Qilu petrochemical co.,ltd. of Sinopec is also facing increasing pressure on energy conservation. In view of the actual problem of high power consumption in the third circulating water plant of ethylene water supply workshop(hereinafter referred to as " three circulation", the same as the following), In 2015.through a series of technological renovation measures such as optimizing the energy-saving operation mode of the circulating water system, updating high-efficiency and energy-saving circulating water pumps,adding frequency conversion equipment for circulating water pumps and cooling fans, and strengthening energy-saving management, the electricity consumption gradually decreased, and the energy-saving effect gradually appeared, reaching the expected set target. Since Sanxun implemented the energy-saving optimization and automatic control system transformation and put it into operation, the process indexes are controllable, the equipment parameters are normal,the circulating water pump and cooling fan run smoothly,and the current situation of high power consumption of the system has been significantly improved. After 11 months of energy-saving optimization operation, a total of 5.547 million kW.h of electricity has been saved, and 3.225 million yuan of efficiency has been created, and good energy-saving effects have been achieved.
引文
[1]陆煜康,唐锂.水处理节能和新能源的应用[M].北京:化学工业出版社,2010:28-38.
    [2]魏新利,付卫东,张军.泵与风机节能技术[M].北京:化学工业出版社,2010:127-142.
    [3]晋卫.水务运营管理与技术[M].北京:中国石化出版社,2013:235-241.
    [4]何晓林,.离心式水泵的选型与节能[C]//工业水处理技术(第九册),北京:中国石化出版社,2005:174-176.
    [5]戴俊明.基于变频器电动水泵调速控制工作原理及定量节能分析[C]//工业水处理技术(第十册),北京:中国石化出版社,2006:502-504.
    [6]丁均胜.变频调速器在供排水设备必造中的应用[C]//工业水处理技术(第十一册),北京:中国石化出版社,2008:220-225.

© 2004-2018 中国地质图书馆版权所有 京ICP备05064691号 京公网安备11010802017129号

地址:北京市海淀区学院路29号 邮编:100083

电话:办公室:(+86 10)66554848;文献借阅、咨询服务、科技查新:66554700