医疗建筑中的联排内衬风管风井施工技术
详细信息    查看全文 | 推荐本文 |
  • 英文篇名:Construction Technology for Rows of Lining Air Ducts and Air Shaft in Medical Building
  • 作者:徐汉文 ; 王超锋 ; 刘国桢 ; 刘可可 ; 杨鹏 ; 李毅 ; 李艳
  • 英文作者:XU Hanwen;WANG Chaofeng;LIU Guozhen;LIU Keke;YANG Peng;LI Yi;LI Yan;The Northwest Company of China Construction Third Engineering Bureau;
  • 关键词:医疗建筑 ; 内衬风管 ; 工序穿插 ; 隔墙材料改进
  • 英文关键词:medical building;;lining air duct;;interspersed working procedure;;partition wall material improvement
  • 中文刊名:JZSG
  • 英文刊名:Building Construction
  • 机构:中建三局建设工程股份有限公司西北公司;
  • 出版日期:2019-06-25
  • 出版单位:建筑施工
  • 年:2019
  • 期:v.41;No.338
  • 语种:中文;
  • 页:JZSG201906022
  • 页数:3
  • CN:06
  • ISSN:31-1334/TU
  • 分类号:77-79
摘要
医疗建筑对通风系统的密闭性、洁净度及温度等要比常规建筑高很多,且其联排内衬风管的通风井道较多、风井建筑空间有限、工序穿插较多,容易出现风井砌体砌筑后风管无法安装、风管安装后风井隔墙无法砌筑、构造柱无法合模等问题。结合某医疗建筑项目风井砌体与风管的设计,对现场施工工序以及隔墙材料作了改进,解决了医疗建筑项目中风井建筑空间有限、风井砌体与风管立管间距不满足安装要求等问题,可供类似工程施工参考。
        The requirements for the airtightness, cleanliness and temperature of the ventilation system of medical buildings are much higher than those of the conventional buildings such as residential buildings and office buildings,resulting in more ventilation shafts for rows of lining air ducts, limited construction space for the air shafts, and more interspersed working procedures, so it is easy to cause problems that the air ducts cannot be installed after the air shaft masonry is built, the air shaft partition wall cannot be built after the air ducts are installed, and the mould for structural column cannot be closed. Combined with the design of air shaft masonry and air ducts of a medical building project, the on-site construction procedure and the partition wall materials were improved, which solved the problems of the limited construction space of the air shaft in the medical building, and the insufficient distance of installation between the air shaft masonry and the air duct riser and provided a reference for similar engineering construction.
引文
[1]白露,魏丰越,江敏,等.内衬风管施工工艺浅析[J].中国设备工程,2017(13):103-104.
    [2]曹勤.某超高层写字楼竖向贯通风井设计[J].暖通空调,2012,42(7):84-87.