济南郊区隧道接地外护套环流对电缆影响检测模拟分析
详细信息    查看全文 | 推荐本文 |
  • 英文篇名:Simulated Analysis on Influence of Circulating Current on Cables in Outer Sheath of Tunnel Ground in Jinan Suburbs
  • 作者:逯遥 ; 姜涛 ; 葛少伟 ; 李德泉 ; 牟泽刚
  • 英文作者:Lu Yao;Jiang Tao;Ge Shaowei;Li Dequan;Mu Zegang;State Grid Jinan Power Company;
  • 关键词:接地外护套 ; 环流 ; 电缆影响 ; 模拟分析
  • 英文关键词:grounding outer sheath;;circulation;;cable influence;;simulation analysis
  • 中文刊名:KJTB
  • 英文刊名:Bulletin of Science and Technology
  • 机构:国网济南供电公司;
  • 出版日期:2019-04-30
  • 出版单位:科技通报
  • 年:2019
  • 期:v.35;No.248
  • 语种:中文;
  • 页:KJTB201904013
  • 页数:4
  • CN:04
  • ISSN:33-1079/N
  • 分类号:82-85
摘要
为了研究隧道接地外护套环流对电缆产生的影响,需要模拟分析隧道接地外护套环流对电缆的影响。当前电缆故障检测方法得到的接地外护套环流值精准度较低,接地外护套环流对电缆影响的模拟分析结果与实际结果不符。以济南郊区隧道为例,模拟分析隧道接地外护套环流对电缆的影响,在分析隧道高压电缆结构的基础上构建金属护套环流计算模型,根据计算结果模拟分析隧道接地外护套环流对电缆的影响,得到的模拟分析结果为当接地外护套环流小于等于设置的阈值时,电力电缆正常工作;当接地外护套环流大于设置的阈值时,接地不正常的部位温度过高,引燃电缆接地外护套的绝缘材料,造成电力电缆被烧毁。实验结果表明,所提方法可准确的测得接地外护套环流值,所提方法模拟分析的结果与实测得到的结果相符。
        In order to study the influence of the circulation of the outer jacket of the tunnel on the cable, it is necessary to simulate and analyze the effect of the circulation of the outer sheath of the tunnel on the cable. The accuracy of the circulating current value of the grounded outer jacket obtained by the current cable fault detection method is low, and the simulation analysis result of the influence of the circulating current of the grounded outer jacket on the cable does not conform to the actual results. Taking the Jinan suburban tunnel as an example, the influence of the circulating current of the outer jacket of the tunnel on the cable is simulated and analyzed. The circulation calculation model of the metal jacket is constructed on the basis of the analysis of the high voltage cable structure of the tunnel, and the tunnel grounding outer sheath circulation current is simulated and analyzed based on the calculation results. The impact of the simulation results obtained is that when the circulating current of the grounding outer jacket is less than or equal to the set threshold, the power cable works normally; when the circulating current of the grounded outer jacket is greater than the set threshold, the temperature of the abnormally grounded location is too high, and the ignition occurs. The insulating material of the outer jacket of the cable grounding causes the power cable to be burned. The experimental results show that the proposed method can accurately measure the circumfluence of the grounded outer jacket. The simulation results of the proposed method are consistent with the measured results.
引文
[1] 敖富荣.500kV高压电缆外手护套环流在线监测装置故障分析与处理[J].水力发电,2017,43(4):23-25.
    [2] 刘炎,裴久杨,樊志新.挤压轮转速对大管径电缆铝护套连续包覆成形的影响[J].锻压技术,2016,41(7):102-109.
    [3] 庞亚宏,双凯,孙奇俏,等.高速测井电缆传输系统的自适应均衡技术研究[J].电子设计工程,2017,25(5):154-157.
    [4] 李红雷,贺林,杨凌辉,等.城市电网设计中电缆通道负载流量优化控制[J].计算机仿真,2017,34(10):83-86.
    [5] 金光,李建龙.基于参数辨识的永磁同步电机电流预测控制方法[J].科技通报,2017,33(7):174-178.
    [6] 陈长浩,王安.一种便携式信号电缆接地故障检测仪[J].计算机测量与控制,2017,25(7):317-319.
    [7] 张建国,徐航,马荔,等.面向电缆故障检测的布尔混沌时域反射法[J].工矿自动化,2016,42(1):35-39.

© 2004-2018 中国地质图书馆版权所有 京ICP备05064691号 京公网安备11010802017129号