摘要
针对蓄电池的开路故障,根据蓄电池发生开路故障的运行特性,研究设计一种温控旁路型电池开路保护器,可实现自动判断并快速解决电池开路故障,从而保护蓄电池组正常对外供电运行。该开路保护器,采用无源工作方式,利用快恢复功率二极管作为启动元件来自动判断并短接处理开路故障电池,利用旁路温控开关来解决快恢复严重发热问题,维持长期运行。
Aiming at the open circuit fault of storage battery, according to the operating characteristics of open-circuit fault of storage battery, a kind of temperature-controlled bypass battery open-circuit protector is designed, which can automatically judge and solve the open-circuit fault of battery quickly, so as to protect the normal external power supply operation of storage battery pack. The open-circuit protector adopts passive mode, uses fast recovery power diode as starting component to automatically judge and bypass open-circuit faulty batteries, and uses bypass temperature control switch to solve the serious heating problem of fast recovery, and maintains long-term operation.
引文
[1]张耀东,李国强,孙照辉.变电站蓄电池的常见故障及其维护方法[J].中国高新技术企业,2015(17):88.ZHANG Yaodong,LI Guoqiang,SUN Zhaohui.Common faults of batteries in substations and maintenance methods[J].China High-tech Enterprises,2015(17):88.
[2]张庆伟,吴玉柱,冯义.变电站蓄电池组开路保护方法研究[J].江西电力职业技术学院学报,2016,29(9):6-9.ZHANG Qingwei,WU Yuzhu,FENG Yi.Research on open-circuit protection method of battery pack in substation[J].Journal of Jiangxi Vocational and Technical College of Electricity,2016,29(9):6-9.
[3]桂长清,柳瑞华.阀控密闭铅酸蓄电池的开路电压变化规律[J].通信电源技术,2007,24(1):61-62.GUI Changqing,LIU Ruihua.Opencircuit voltage of VRLA battery[J].Telecom Power Technologies,2007,24(1):61-62.