摘要
在ASHRAE2008绿色数据中心扩大的热环境前提要求下,假定交叉式露点间接蒸发冷却空调机组处理过程为等湿冷却,且送回风温差为10℃,以此确定极端的送风参数范围。利用该送风参数范围,再结合《中国建筑热环境分析专用气象数据集》,对新疆干燥地区两个典型城市的单独运行交叉式露点间接蒸发冷却空调机组进行了小时数统计,值得大力推广发挥其较大的节能潜力。
In ASHRAE2008 expanding green data center thermal environment requirements premise assumes cross dew point indirect evaporative cooling air conditioning units and other processes to wet cooling, and the return air temperature difference is 10℃. According to aboving, we can determine potential the extreme air parameters. With this air parameters,combined with "China building thermal environment analysis dedicated meteorological data sets", cross dew point indirect evaporative cooling air conditioning units run hours to statistics on the two separate cities in Xinjiang dry areas typical.Play its worth promoting in order to greater energy saving potential.