摘要
国内主流厂家对于CT断线功能理解差异较大,保护相关标准中CT断线方面的性能指标要求较少,该文提出CT断线功能的一些重要性能指标;介绍国内主流厂家母线保护的CT断线功能,指出存在的不足;提出智能变电站CT断线特征的概念,对智能变电站母线保护的CT断线特征进行了分析;充分利用智能变电站信息共享的优势,设计新的母线保护CT断线功能实现方案,提升CT断线功能的性能指标,适应智能变电站的应用,给智能变电站保护相关标准的制定、运行维护、保护装置研制等提供参考。
There are large differences between major domestic manufacturers about understanding CT line-break function,and there are a few requirements about CT line-break performance index in protection standards.Some important performance indexes of CT linebreak functions are put forward in this paper;CT line-break functions about busbar protection IEDs of major domestic manufacturers are introduced,and the deficiencies are pointed out;The author puts forward a concept about CT line-break features in smart substation, and CT line-break features are analyzed about busbar protection in smart substation;the author makes full use of the advantages of information sharing in smart substation,and designs a new scheme of CT line-break functions about busbar protection to improve performance indexes of CT line-break function,to adapt to the application of smart substation,and provides the reference for protection standard setting,operation maintenance,and protection design etc.of smart substation.
引文
[1]中国标准出版社.GB/T 14285-2006继电器保护和安全自动装置技术规程[S].北京,2006.
[2]中国电力出版社.DL/T 670母线保护装置通用技术条件[S].北京,2010.
[3]易永辉,王雷涛,陶永健.智能变电站过程层应用技术研究[J].电力系统保护与控制,2010,38(21):1-5.YIYong-hui,WANGLeitao,TAO Yong-jian.Process level appl ication scheme in smart substation[J].POWER SYSTM PROTECTION AND CONTROL,2010,38(21):1-5.
[4]深圳南瑞科技股份有限公司.BP-2C微机母线保护装置说明书[Z].2008(9).
[5]北京四方继保自动化股份有限公司.CSC-150数字式母线保护装置说明书[Z].2006(4).BEIJIN SIFANG AUTOMATION CO.,LTD.CSC-150 digital busbar protection[Z].2006(4).
[6]国电南京自动化股份有限公司.SGB-750数字式母线保护装置说明书[Z].2013(7).
[7]樊陈,倪益民,窦仁辉,等.智能变电站过程层组网方案分析[J].电力系统自动化,2011,35(18):67-70.FAN Chen,NI Yimin,DOU Renhui,SHEN Jian,GAO Chunlei,HUANG Guofang.Analysis of Network Scheme for ProcessLayer in Smart Substation[J].Automation of Electric Power Systems,2011,35(18):67-70.
[8]文明浩.线路纵差保护CT二次断线判据分析[J].继电器,2006,34(18):1-3.WEN Ming-hao.Analysis of second loop break criterion of CT used in differential protection of transmission line[J],RELAY,2006,34(18):1-3.
[9]徐小龙,游大海,尹项根.方向式母线保护的探讨和应用[J].电力系统自动化,2003,27(22):80-81.XUXiao-long,YOU Da-hai,YINXiang-gen.A PPLICATION OF COMMUNICATIO NBASED DIRECTIONAL BUSBAR PROTECTION[J].Automation of Electric Power Systems,2003,27(22):80-81.