摘要
通过试验发现升压速率对于水带的爆破压力值有较为显著的影响,特别是爆破压力处于标准规定的最低值附近的产品,很可能会出现合格和不合格两种完全不同的结论。采用试验研究不同升压速率对消防水带爆破压力值的影响,试验结果表明:标准范围内的升压速率值都能很好地满足水带爆破所需的升压速率要求;升压速率为7 MPa/min时,对应一组水带爆破压力的最大值,选择爆破压力最大值对应的升压速率作为水带爆破压力值的检出值对产品本身判定最为有利,同时也能减少对水带质量检测结果的错判风险。
It is found that the boost rate has a significant effect on the blasting pressure of fire hose, especially for the products whose blasting pressure is near the lowest value specified in the standard,there are likely to be two completely different conclusions: qualified and unqualified. In this paper, the effects of different boost rates on the bursting pressure of fire hose are studied by experiments. The results show that the boost rate values within the standard range can meet the requirements of the boost rate for water blasting. When the boost rate is 7 MPa/min, the corresponding maximum blasting pressure is selected as the detection value of blasting pressure value, which is most favorable for judging the product itself, and at the same time reduces the risk of misjudging the detection results of fire hose's quality.
引文
[1]景绒,侯耀华,李进兴,等.新型消防水带水力技术参数的实验研究[J].消防科学与技术,2014,33(3):310-313.
[2]魏振堃,蒋明,张起欣,等.内压作用下聚氨酯消防水带管径变化研究[J].消防科学与技术,2017,36(1):86-89.
[3]金富.浅谈消防水带爆破压力试验结果影响因素[J].品牌与标准化,2016,(4):76-77.
[4]丁卓群,柯志鹏.消防水带爆破压力试验中爆破压力与升压速率关系分析研究[J].福建建材,2017,(2):1-3.
[5]李渠成,汪志宏,陈伟浪.热空气老化时间对消防水带质量性能影响研究[J].科技与创新,2018,(19):55-56.
[6]于智,智放.新型消防水带的研制[J].世界橡胶工业,2006,(10):18-20+51.