Operation of displacement ventilation (DV) and evaporative cooled ceiling (ECC) system is modeled.
•
The DV/ECC model was validated experimentally at different supply conditions and fixed load.
•
Desiccant dehumidification was added to DV/ECC system for operation in humid climate.
•
DV/ECC performance is optimized using genetic algorithm for minimum energy cost.
•
DV/ECC operation at optimal conditions reduced cost by 28% compared to DV/chilled ceiling system.
NGLC 2004-2010.National Geological Library of China All Rights Reserved.
Add:29 Xueyuan Rd,Haidian District,Beijing,PRC. Mail Add: 8324 mailbox 100083
For exchange or info please contact us via email.