Optimized performance of displacement ventilation aided with chair fans for comfort and indoor air quality
详细信息    查看全文
文摘

The performance of displacement ventilation (DV) system aided with chair fans (CF) is optimized.

A CFD model and bio-heat model were used in the simulations to assess comfort and air quality.

The model was validated experimentally using a thermal manikin seated on a chair equipped with fans.

Optimal fan height is between 30 and 31 cm above the floor at fan total flow rate of 12 m L/s.

Compared to stand alone DV system without chair fans, energy savings ranged between 20.6% and 11.6%.